Permit: T04EL01124

Parcel: 122173090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01124

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/28/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PERMANENT ADDRESS OR NUMBER ON RV RECEPTACLES. 2) EXPOSE GROUND ROD AND CLAMP. 3) WIRING IN RECEPTACLE INCORRECT, COPPER TO PLUM AND TWO CONDUCTORS TAPED RED. 4) THE WIRING AT DISCONNECTS DIFFERANT THAN AT BOXES. 5) THE SERVICES ARE IN NEED OF REPAIRS, ESPECIALLY THE BOARD SUPPORT AND GUTTER. THE WIRING AT RV RECEPT. BEING SMALLER ALUM. THAN AT SERVICES INDICATES A SPLICE IN THE LINE, THIS NEEDS TO BE REVIEWED. 6) RV RECEPTS ARE 120V. 30A. FUSES AT SERVICE ARE 40A. SUGGEST SERVICES BE UPGRADED.