Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/18/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 05/28/2004 |
ELECTRIC - FINAL |
|
Denied |
1) PERMANENT ADDRESS OR NUMBER ON RV RECEPTACLES. 2) EXPOSE GROUND ROD AND CLAMP. 3) WIRING IN RECEPTACLE INCORRECT, COPPER TO PLUM AND TWO CONDUCTORS TAPED RED. 4) THE WIRING AT DISCONNECTS DIFFERANT THAN AT BOXES. 5) THE SERVICES ARE IN NEED OF REPAIRS, ESPECIALLY THE BOARD SUPPORT AND GUTTER. THE WIRING AT RV RECEPT. BEING SMALLER ALUM. THAN AT SERVICES INDICATES A SPLICE IN THE LINE, THIS NEEDS TO BE REVIEWED. 6) RV RECEPTS ARE 120V. 30A. FUSES AT SERVICE ARE 40A. SUGGEST SERVICES BE UPGRADED |