Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/03/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection :* |
| 06/01/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection :*/ 1) CLEAN SURFACE UNDER GROUND BAR - 250.12. 2) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250-8. 3) LARGER THAN #8 NOT ALLOWED IN RACEWAY - SOLID. NEED TO BE STRANDED. |