Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK TO CLEAR | |
| 07/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection. We still have loose fittings. 1 conductor to a neutral terminal. Cannot use stranded and solid under terminal 4) cannot " trim" conductors to fit |
|
| 06/02/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) TIGHTEN LOOSE FITTINGS. 2) ADDRESS LABEL TO BE SCREWED OR RIVITED. 3) FINISH ITEMS 2-6 OF PREVIOUS INSP. 4) TIGHTEN LOOSE TERMINATIONS. |
|
| 05/27/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 2) GAS AND WTR BONDS TO BE TO INTERIOR SIDE OF PIPING. 3) USE APPROVED FITTINGS TO CONDUITS - CHASE NIPPLES - LOCK NUTS AS SPACERS NOT APPROVED. 4) FILL UNUSED OPENINGS AND USE REDUCING WASHERS AS LISTED. 5) USR CORRECT SIZE CONDUCTOR TO SPLICE NEUTRAL AND GROUND #10 TO #2 NOT ALLOWED. 6) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG. |