Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/21/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) REINSTALL ADDRESS LABEL WITH ALL NUMBERS PER ADDRESS, LABEL READS 354 E. 2) INSTALL FUSES, REJECTION PINS. | |
| 06/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL 3/4" X 10' GROUND RODS AS INDICATED ON APPROVED PLAN - CONTRACTOR USED ½". 2) BOND GAS AND BLD STEEL AS WELL AS WATER - 250-104 NEC. 3) BOND BUSHINGS REQUIRED ON BOTH SIDES OF NIPPLES 250-94 NEC. 4) MAINTAIN 1/0 CU. GROUND THRU OUT SYSTEM INTO CT CAN GROUND GUTTER. |