Permit: T04EL01085

Parcel: 13013044A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/12/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/21/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) REINSTALL ADDRESS LABEL WITH ALL NUMBERS PER ADDRESS, LABEL READS 354 E. 2) INSTALL FUSES, REJECTION PINS.
06/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL 3/4" X 10' GROUND RODS AS INDICATED ON APPROVED PLAN - CONTRACTOR USED ½". 2) BOND GAS AND BLD STEEL AS WELL AS WATER - 250-104 NEC. 3) BOND BUSHINGS REQUIRED ON BOTH SIDES OF NIPPLES 250-94 NEC. 4) MAINTAIN 1/0 CU. GROUND THRU OUT SYSTEM INTO CT CAN GROUND GUTTER.