Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :*1) OK TO CLEAR | |
| 05/28/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICE MUST HAVE A PERMANENT METAL ADDRESS TAG SCREWED TO COVER. 2) SERVICE WIRES IN RISER MUST BE TAPED WHITE CLOSER TO WEATHER HEAD AND INSIDE SERVICE ALSO. 3) GAS BOND IS ON PLASTIC COVERING, SHOULD BE ALL METAL. 4) ½" CONDUIT BELOW SERVICE MUST HAVE A FITTING INTO PANEL AND A GROUND CLAMP AT BOTTOM WHICH ALSO TIES TO GROUND WIRE. 5) THE 2" RISER ABOVE PANEL - THE TWO STRAPS HOLDING RISER MUST HAVE BACKING - THEY ARE LOOSE. |