Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/24/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICES TO BE PHASED FOR 220 VOLTS. 2) WE HAVE MULTIPLE TERMINATIONS UNDER LUGS. 3) WE HAVE SECONDARY CONDUCTOR PASSING THRU UNPROTECTED CONDUCTORS SECTIONS 230-7. 4) PROTECT CONDUCTOR FROM SHARP METAL EDGES. 5) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 250-24. 6) PLEASE ADDRESS 2ND BOILING DISCONNECT MEANS. 7) SEPERATE GROUNDS AND NEUTRALS. 8) MAIN BREAK TO HAVE MANUFACTURERS HOLD DOWN DEVICE |