Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/07/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/24/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SERVICES TO BE PHASED FOR 220 VOLTS. 2) WE HAVE MULTIPLE TERMINATIONS UNDER LUGS. 3) WE HAVE SECONDARY CONDUCTOR PASSING THRU UNPROTECTED CONDUCTORS SECTIONS 230-7. 4) PROTECT CONDUCTOR FROM SHARP METAL EDGES. 5) GROUNDING ELECTRODE CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 250-24. 6) PLEASE ADDRESS 2ND BOILING DISCONNECT MEANS. 7) SEPERATE GROUNDS AND NEUTRALS. 8) MAIN BREAK TO HAVE MANUFACTURERS HOLD DOWN DEVICE