Permit: T04EL01080

Parcel: 116160810


Addresses:

517 W OURY ST #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/07/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*/DENIED
PLEASE SUBMIT A PLAN OF THE ELECTRICAL SERVICE, LOAD CALCULATIONS, AND FLOOR PLANS FOR EACH APARTMENT UNIT. THE WORK IS A COMPLETE REWIRE-NOT SIMPLY A SERVICE UP GRADE.
05/24/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/UNITS ARE IN UNSAFE WIRING CONDITIONS - NOTIFIED MINIMUM HOUSING. 1) SERVICES TO BE PHASED FOR 220 VOLTS. 2) WE HAVE MULTIPLE TERMINATIONS UNDER LUGS. 3) WE HAVE SECONDARY CONDUCTOR PASSING THRU UNPROTECTED CONDUCTORS SECTIONS 230-7. 4) PROTECT CONDUCTOR FROM SHARP METAL EDGES. 5) GROUNDING CONDUCTOR TO TERMINATE AT GROUNDED TERMINAL 250-24.