Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/13/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) COLOR CODE FOR SERVICE CONDUCTORS NOT CORRECT 2) NO COMPLIANCE WITH NOTE #3 LAST INSPECTION 3) HAVE C-11 LICENSED CONTR. |
|
| 06/09/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL PERM. ADDRESS LABEL ON NEW SERVICE DISCONNECT SW. MUST BE SCREWED OR RIVITED TO ENCLOSURE. 2) I.D. SERVICE AND LOAD CONDUCTORS WITH PROPER COLOR CODE I.D. TAPE. 3) RECEPTS ON ROOF EXCEPT COOLER MUST BE GFI AND IN W/P BOXES AND COVERS. |
|
| 05/27/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) INSTALL UNIT NO. ABOVE DOOR. 2) PLUG UNUSED OPENINGS IN RECEPT BOX, NORTHEAST ROOM AND AT SMALL DISCONNECT SWITCH SOUTHWALL. 3) SPLICES OUTSIDE SOUTH WALL NEED TO BE IN APPROVED J-BOX. 4) DISCONNECT OUTSIDE SOUTH WALL NOT WIRED PROPERLY AND NOT APPROVED FOR OUTDOOR USE, MULTIPLE TAPS NOT ALLOWED, ALSO WIRING IN DISCONNCT BELOW SERVICE. 5) SERVICE NOT GROUNDED GROUND PER CODE - ART 250 NEC. 6) CALL TEP. TO REMOVE LOCK ON DISCONNECT FOR INSP. 7) OPEN UNIT 2 TO INSPECT WIRING PASSING THRU TO UNIT 1. WORK MUST BE DONE BY L-11 LICENSED CONTR. 8) PROVIDE LADDER FOR ROOF INSP. |