Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/23/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/DENIED 1) RISER CONDUITS MISSING CONDUCTORS. 2) BOND LOCKMUTS USED ON CONCENTRICS NOT EFFECTIVE DUE TO SET SCREW PUSHING OUT CON CENTRICS. USE BOND BUSHINGS. 3) SHEET METAL SCREWS NOT ALLOWED FOR MECA LUG? BONDING 4)BOND WIRE TO SMALL ON 4" NIPPLES 5) NO ADDRESS LABELS ON METER BASES 6) INSTALL FUSEES-R-PINS |
|
| 07/22/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |