Permit: T04EL01058

Parcel: 118121000


Addresses:

1317 S 6TH AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/24/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
08/23/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/DENIED
1) RISER CONDUITS MISSING CONDUCTORS.
2) BOND LOCKMUTS USED ON CONCENTRICS NOT EFFECTIVE DUE TO SET SCREW PUSHING OUT CON CENTRICS. USE BOND BUSHINGS.
3) SHEET METAL SCREWS NOT ALLOWED FOR MECA LUG? BONDING
4)BOND WIRE TO SMALL ON 4" NIPPLES
5) NO ADDRESS LABELS ON METER BASES
6) INSTALL FUSEES-R-PINS
07/22/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*