Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL01034
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK FINAL | |
06/21/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ PLEASE COMPLETE ITEMS 1, 2, 4, 5, & 7 OF PREVIOUS INSP. |
|
06/15/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CONDUITS ARE KINKED - USE APPROVED BENDING METHODS FOR CONDUIT. 2) SERVICE BOARD TO USE SUITABLE HARDWARE NOT DRYWALL SCREWS. 3) RISER HARDWARE TO BE ΒΌ" MIN. 4) PLEASE VERIFY WTR AND GAS BONDING PER 250-104. 5) GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN OR OTHER THAN WHITE ENTIRE LENGTH, 200-7, 250-119. 6) A PERMAMENT METAL ADDRESS LABEL IS NEEDED. 7) OWNER STATES AN ELECTRITIAN IS DOING WORK. PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR. |