Permit: T04EL01034

Parcel: 133261500


Addresses:

8128 E 4TH PL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL01034

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK FINAL
06/21/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ PLEASE COMPLETE ITEMS 1, 2, 4, 5, & 7 OF PREVIOUS INSP.
06/15/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) CONDUITS ARE KINKED - USE APPROVED BENDING METHODS FOR CONDUIT. 2) SERVICE BOARD TO USE SUITABLE HARDWARE NOT DRYWALL SCREWS. 3) RISER HARDWARE TO BE ΒΌ" MIN. 4) PLEASE VERIFY WTR AND GAS BONDING PER 250-104. 5) GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN OR OTHER THAN WHITE ENTIRE LENGTH, 200-7, 250-119. 6) A PERMAMENT METAL ADDRESS LABEL IS NEEDED. 7) OWNER STATES AN ELECTRITIAN IS DOING WORK. PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR.