Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T04EL01030
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/19/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :*/ 1) OK TO CLEAR 2) NOTE TO CONTRACTOR STRAP #4 GROUND WIRE TO PEDESTAL | |
05/18/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ NEED A PERMANENT METAL ADDRESS TAG. - MARKER NO LONGER APPROVED. 2) GROUND RODS TO BE 30" BELOW GRADE. 3) GROUND WIRE FROM RODS TIED IN WRONG PLACE NEEDS TO BE WHERE BREAKER COMPARTMENT IS - IT TIES TI NUETRAL THERE. |