Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/16/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/11/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) THE SERVICE REQUIRES 3' OF CLEARANCE IN FRONT OF AND AS WIDE AS THE SERVICE DOWN TO GROUND THE WATER LINES BELOW SERVICE ARE IN THE WAY 2) 1" CONDUIT GOING UP WALL NEEDS TO BE SECURED 3) 1" ENTRY INTO WEST SIDE OF PANEL. NEEDS TO BE COMPLETELY SEALED BECAUSE IT IS ABOVE BUS LINE |