Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/21/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 05/20/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 05/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) NE ENTRANCE THROUGH METER SECTION 230-7 AND MANUFACTURERS INSTRUCTIONS. 2) FILL UNUSED OPENINGS WHERE GROUND CONDUCTOR ENTERS. 3) GROUNDING ELECTRODES TO BE CLOSER TO SERVICE 250-30(A)(3). 4) PLEASE MOVE GAS BOND TO INTERIOR SIDE OF UNION. |