Permit: T04EL00977

Parcel: 133260820


Addresses:

542 N KENT DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/19/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/14/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) BONDING JUMPER FOR GROUNDING EQUIPMENT CONDUCTORS TO BE SIZED PER 250-122 - JUNCTION BOX. 2) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING. 3) USE AN APPROVED CONNECTION FOR COPPER TO ALUMINUM. 4) RED WIRE NUTS NOT LISTED FOR USE WITH LARGE CONDUCTORS. 5) PLEASE IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD.