Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/02/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK TO CLEAR ECO |
| 05/26/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ CHASE NIPPLE NOT AN APPROVED FITTING - USE AN APPROVED FITTING. |
| 05/19/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) A PERMANENT METAL ADDRESS LABEL IS NEEDED. 2) PLEASE VERIFY 2ND GROUND ROD. 3) A BONDING DEVICE IS NEEDED FOR RISE. 4) UNDERGROUND CONDUITS COVERED WITHOUT INSPECTION - PLEASE UNCOVER. 5) INSTALL OVERCURRENT DEVICE AND TERMINATE CONDUCTOR. LABEL PANEL AFTER INSTALLATION |