| 11/23/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) OK FINAL |
| 11/22/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 11/16/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/1)LABEL BREAKERS 2)FILL UNUSED OPENINGS 3)SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING USE GROUND SCREW |
| 09/07/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
1) PLEASE MOVE WATER TO GAS BOND ON OTHER SIDE OF ? ELECTRIC UNION. 2) PLEASE RECALL AFER CROSSOVER COMPLETE. OK TO CLEAR |
| 06/02/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE 110-26. 2) A PERMAMENT METAL ADDRESS LABEL IS NEEDED. 3) RISER TO BE ΒΌ" MIN. HARDWARE. 4) PLEASE VERIFY GAS BOND. 5) NEED TO SEE CONNECTIONS AFTER CROSSOVER. |