Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL00952

Parcel: 121123110


Addresses:

1401 N MAGNOLIA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/23/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK FINAL
11/22/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
11/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/1)LABEL BREAKERS 2)FILL UNUSED OPENINGS 3)SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING USE GROUND SCREW
09/07/2004 ELECTRIC - FINAL Partial Approval 1) PLEASE MOVE WATER TO GAS BOND ON OTHER SIDE OF ? ELECTRIC UNION. 2) PLEASE RECALL AFER CROSSOVER COMPLETE. OK TO CLEAR
06/02/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) MAINTAIN WORKING CLEARANCES IN FRONT OF SERVICE 110-26. 2) A PERMAMENT METAL ADDRESS LABEL IS NEEDED. 3) RISER TO BE ΒΌ" MIN. HARDWARE. 4) PLEASE VERIFY GAS BOND. 5) NEED TO SEE CONNECTIONS AFTER CROSSOVER.