Permit: T04EL00947

Parcel: 137061210


Addresses:

401 W OREGON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) NOTES: EXPOSE GROUND RODS FOR INSPECTION-2 REQUIRED 6' MINIMUMN APART 2) INSTALL PERMNAENT ADDESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO COVER 3) FILL IN UN-USED BEAKER SLOTS 4) BOND GAS PIPE