Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/12/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) NOTES: EXPOSE GROUND RODS FOR INSPECTION-2 REQUIRED 6' MINIMUMN APART 2) INSTALL PERMNAENT ADDESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO COVER 3) FILL IN UN-USED BEAKER SLOTS 4) BOND GAS PIPE |