Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T04EL00937
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/07/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1)ONLY ONE NEUTRAL CONDUIT PER TERMINAL - PLEASE SPEARATE 2)FILL UNUSED OPENING IN GUTTER, DSCONNECT 3) PROTECT CONDUCTORS AT BACK OF DISCONNECT 4) WE HAVE MULTIPOLE TERMINATIONS AT MAIN DISCOUNT 5) MAIN DISCOUNT TO BE REPLACED. CENTER FUSEHOLDER IS BEING HELD TOGETHER WITH A MAKE SHIFT MEANS CLAMP. 6) REPLACE MISSING GUTTER SCREWS 7) A LICENSED ELECTRICAL CONTRACTOR TO DO WORK. |