Permit: T04EL00936

Parcel: 12315105A


Addresses:

724 E ADAMS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/09/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/07/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ PROVIDE AN APPROVED PLAN CANNOT LOCATE ONE ON SITE.
05/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THERE IS ONLU ONE METER LOOP ON THIS PERMIT AND THERE ARE 4 INVOLVED ON ONE SERVICE (ADD 3 LOOPS AND OTHER ADDRESSES TO THIS PERMIT.)
2) PROVIDE AN APPROVED PLAN TO VERIFY SIZE OF SERVICE ENTRANCE CONDUCTORS.
3)WATER BOND AND GAS BOND LOCATIONS LOCKED.
4) BARE COPPER (4#) ON WALL TO BE STRAPPED