Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/18/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*/ 1) OK TO CLEAR RECONNECT, OK TO RE-ENERGIZE
05/17/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
Install 2 ground rods 6 feet apart with a continuous grounding electrode conn/ 1) YOUR INSTALLATION DOES NOT COMPLY WITH TEP STANDARDS. SEE TEP INFO SHEET. 2) A COMPLETE NEW GROUND SYSTEM CONSITING OF TWO 5/8"X8' GROUND RODS, CONNECTION TO COLD WTR PIPE AND METAL GAS PIPING IS REQUIRED. EXISTING GROUND IS UNPROVEN THERFORE UNACCEPTABLE. 3) THE PANEL MUST BE FASTENED TO THE WALL WITH ΒΌ" MIN. HARDWARE. USING LAG BOLT AND ANCHORS. SEE TEP SR 305 REQUIREMENTS. CONTACT TEP ABOUT ITEMS NOTED.