Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00919
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/OK TO CLEAR | |
| 10/04/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| BREAKERS IN PANEL NEED TO BE SAME BRAND WIRE SIZE TO BREAKERS MUST BE CORRECT SEPERATE GROUNDS & NEUTRALS |
|
| 10/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection :WIRING IN PANEL TO BE CONNECTED BY LIC ELEC CONTRACTOR ISOLATE GROUNDS & NEUTRALS REMOVE DOUBLE LUGGING SEAL HOLE & INSTALL PANEL COVER |
|
| 09/29/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 09/21/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1) DISCONNECT & REMOVE WIRING FROM 1501 PANEL RUN OVER 1505 PANEL. 2) NO EXPOSED ROMEX BELOW 8' WIRING MUST BE IN APPROVED RACEWAY BELOW 8' FROM CEILING. 3) SUPPORT LOOSE OR NON SUPPORTED CONDUIT PER CODE. WORK TO BE DONE BY L11 OR K11 LICENSED CONTR. HAVE CONTR CALL DAN 791-5550 EXT 1136 |