Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/04/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*1) OK TO CLEAR INCREASE 2) NOTE: BLDG HAS POWER NOW, NO BOND REQUIRED | |
| 05/27/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) BOND WTR PIPING BOTH UNITS. 2) BOND BUSHINGS OR BONDING LOCK-NUTS REQUIRED AHEAD OF OVER CURRENT PROTECTION 250-94, 250-104. 3) COMPLETE LOAD WIRING. 4) PROVIDE 6' LADDER OPEN GUTTER FOR INSP. |