Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/05/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 05/04/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FRONT: PANEL WIRING INCORRECT, NEUTRAL TIED TO GROUND WHITE COLORED WIRING TO BE TAPED BLACK, SEAL HOLES BOTTOM OF PANEL 2) ALL DEVICE COVERS AND SWITCH COVERS TO BE INSTALLED ALL OPEN J-BOXES TO HAVE WIRE NUTS AND COVERS 3) WATER HEATER J-BOX TO BE SECURE AND A BUSHING USED FOR BETWEEN J-BOX AND WH. 4) REAR PANEL NEEDS BREAKER COVER 5) ADDRESS SERVICE 6) REMOVE 1/2" CONDUIT WITH OPEN WIRES |