Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR INC NO ANSWER AT DOOR | |
| 10/01/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : NO INSPECTION NO CONTACT. NOTE:UPON CALLING UTR ELECTRIC TO ASK QUESTION THEIR NUMBER NO LONGER IN SERVICE. WILL LEAVE MESSAGE ON IVR SYSTEM STATING THAT INSPECTOR WILL NEED CONTRACTOR TEL. NUMBER, LICENSE NUMBER AND NAME. |
|
| 09/23/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 09/22/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 05/07/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT RISER ABOVE PANEL. 2. STRAP #4 BARE TO WALL AT WATER BOND.. 3. USE SEALING LOCKNUT FOR 1/2" CONDUIT CONNECTOR AT TOP ENTRY. 4. INSTALL CONNECTOR W/BUSHING TO PROTECT CABLE FROM ABRAISION WHERE CABLE EXISTS CONDUIT SLEEVE. 5. ROMEX MUST BE PROTECTED BELOW 8' AT OUTSIDE SWITCH. 6. SUPPORT 1/2" CONDUIT WITHIN 3' OF DRYER RECEPT.. 7. UPGRADE WILL NOT BE APPROVED UNTIL EXPOSED ROMEX WIRING AT BACK PORCH AND FRONT RECPT BY WATER CONDITIONER BROUGHT UP TO CODE. (UNSAFE) |