Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2004 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 07/12/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection (1) PLEASE-REVIEW PREVIOUS WRITE UPS AND OPEN UP WALL SO THAT I CAN INSPECT ALL PREVIOUS WORK. (2) I WILL NEED TO VERIFY FOOTING BELOW POST. OPEN UP SO I CAN VERIFY. (3) SCOTCH COAT SPLICES TO KEEP TAPE IN PLACE. (4) NEED TO OPEN UP WALL SO I CAN VERIFY FRAMING. | |
| 05/12/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) A PERMIT WILL NEED TO BE OBTAINED FOR WORK DONE, PRIOR TO RECONNECTION. 2) CONDUCTORS FROM BLDG TO BLDG MAINTAIN CLEARANCES TO GROUND AND USE APPROVED SPLICES. 3) A MAIN BREAKER IS NEEDED AT 2ND BLDG - 225.30, 225.31. 4) BALANCE LOAD ON PHASES. 5) A LICENSED ELECTRICAL CONTRACTOR IS NEEDED TO PERFORM WORK. |
|
| 05/03/2004 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |