Permit: T04EL00889

Parcel: 11008065A

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
07/29/2004 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
07/12/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection (1) PLEASE-REVIEW PREVIOUS WRITE UPS AND OPEN UP WALL SO THAT I CAN INSPECT ALL PREVIOUS WORK. (2) I WILL NEED TO VERIFY FOOTING BELOW POST. OPEN UP SO I CAN VERIFY. (3) SCOTCH COAT SPLICES TO KEEP TAPE IN PLACE. (4) NEED TO OPEN UP WALL SO I CAN VERIFY FRAMING.
05/12/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) A PERMIT WILL NEED TO BE OBTAINED FOR WORK DONE, PRIOR TO RECONNECTION. 2) CONDUCTORS FROM BLDG TO BLDG MAINTAIN CLEARANCES TO GROUND AND USE APPROVED SPLICES. 3) A MAIN BREAKER IS NEEDED AT 2ND BLDG - 225.30, 225.31. 4) BALANCE LOAD ON PHASES. 5) A LICENSED ELECTRICAL CONTRACTOR IS NEEDED TO PERFORM WORK.
05/03/2004 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*