Permit: T04EL00879

Parcel: 130100340


Addresses:

3225 E 23RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/12/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/10/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) WATER AND PIPING MUST BE BONDED TO NEW SERVICE PER 250.104 NEC. 2) OK TO USE EXISTING GROUND ROD, BUT IT MUST ALSO BE TIED INTO NEW SERVICE
05/03/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) BOND WATER AND GAS PIPING 2) INSTALL PERMANENT ADDRESS LABEL ON ENCLOSURE 3) USE 1/4 MINIMUM BOLTS TO SUPPORT RISER 4) SUPPORT BOX FOR GFI RECEPT