Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/21/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) NOTES: USE APPROVED OUT DOOR J-BOX FOR SPLICES OF EXISTING TO NEW HOUSE FEEDERS 2) ALL FITTINGS ON CONDUIT OUTSIDE MUST BE RAIN TITE. J-BOX ABOVE SERVICE MUST BE RAINTIE 3) USE APPROVED FITTINGS AT LB TERMINATION INTO SERVICE PANEL 4) NEW OUTSIDE RECEPT MUST BE GFI TYPE 5) NO COMPLIANCE WITH LAST INSPECTION NOTES: 2 AND 3. NEED TO VERIFY LICENSED CONTR. DOING WORK LEAVE NAME AND PHONE NUMBER |
|
| 05/12/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) OK TO CLEAR INCREASE 2) POUND GROUND RODS FLUSH WITH GROUND 3) STRAP # 4 BARE TO WALL 4) CALL FOR FINAL AFTER TIE IN |