Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 05/05/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999*. DENIED. Service need to be permanently addressed no marker. Ground rods have to be miniumu 6' apart and the #4 bare copper has to be on opposite end of acorn clamp not bolt side. All PVC use above ground has to be SCH 80. Water bond & Gas bond to be put on this service if it feeds house. Once service changed over how will existing service be left (as far as meter opening). CALLED AT 9:30AM ON SIT AT 10AM (REQUEST 1/2 HR CALL AHEAD) 1) GROUND RODS STILL NOT 6' APART - INCLUDE UNDERGROUND NOT JUST ABOVE GROUND. 2) CANNOT GO THRU TEP METER TWICE, LAST INSPECTION REQUESTED METHOD BYPASS AT EXISTING TEP METER - NOTHING CHANGED. 3) RE-FEE DUE PRIOR TO NEXT INSPECTION. |