Permit: T04EL00841

Parcel: 127050970


Addresses:

4721 E 2ND ST

Inspection Status: Denied

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/22/2006 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/26/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*/ 1) OK TO CLEAR 1) PLEASE RECALL AFTER CROSS OVER
05/12/2004 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
05/03/2004 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*/ 1) PERMANENT METAL ADDRESS LABELS ARE NEEDED 2) GAS AND WATER BONDS ARE REQUIRED 250.104-BOTH UNITS 3) SEALING DEVICES NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 4) PLEASE STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG 5) MAIN OVER CURRENT DEVICE TO BE ACCESSIBLE TO OCCUPANTS 2401.24 6) GUY BACK BRACING WILL BE NEEDED 7) OLD DISCONNECT NOT ALLOWED FOR JUNCTION BOX OR NEED TO BE AMDE WEATHER PROOF 8) YOU HAVE MULTIPLE TERMINATIONS UNDER SVREWS 9) PLEASE IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD 10) PLEASE VERIFY CUT OFF PIECES OF GROUND RODS