Permit: T04EL00839

Parcel: 122070550


Addresses:

4407 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/30/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/23/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/27/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) SOME STRANDS OF GROUNDING EQUIPMENT CONDUCTOR BROKEN - CONDUCTOR SIZE TO REMAIN THROUGHOUT RUN. 2) 8-3 NM CABLE TO BE FUSED AT AMPACITY PER 336. 3) USE APPROVED FITTINGS FOR LB. 4) DISCONNECT NOT TO BE USED AS A PAAS THROUGH. 5) SUPPORT CONDUIT BELOW PANEL. 6) SEALING DEVICE NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 7) SEPERATE GROUNDS AND NEUTRALS AT SUB PANEL.