Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/05/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ KO PLUGS ON TOP OF PANEL MUST BE LISTED FOR OUTSIDE USE. MUST BE RAINTITE TO KEEP WTR OUT. PLUGS USED ARE INDOOR PUSH IN TYPE. |
|
| 05/03/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) TOP ENTRY FOR BRANCH CIRCUITS NOT APPROVED RE-LOCATE CONDUITS TO LOWER SIDE OR BTTOM ENTRY. PROVIDE LISTING ALLOWING TOP ENTRY FOR LOAD CIRCUITS |
|
| 04/29/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*/ 1) GATE LOCKED-RECALL INSP. WHEN ACCESS AVAILABLE |