Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/23/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*/ 1) OK FOR TEMP POWER | |
| 06/11/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) WRONG COLOR CODE ON METER BASE . HAVE WHITE AT LINE. ? TO NEUTRAL. MAKE ALL CORRECT COLOR CODE. A REFEE DUE BEFORE NEXT INSPECTION |
|
| 06/09/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ IDENTIFIED CONDUCTOR TERMINATED AT 2 POLE BREAKER. 2) CANNOT HAVE BARE NEUTRAL TO JUNCTION BOX. IMPROPER FITTING USED TO TERMINATE CONDUIT. TIE-IN NEW GROUNDING SYSTEM TO NEW SERVICE. |
|
| 06/07/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |