Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ OK FINAL - MAINTAIN CLEARANCES IN FRONT OF PANEL. |
| 06/01/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ CANCELLED BY GREY. |
| 05/26/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :*/ 1) CLEAN SURFACE UNDER GROUND BAR AND CANNOT USE SHEET METAL SCREWS. 250-12. 2) WHERE IS 15/2 OVER CURRENT DEVICE AND RECEPTACLE AS PER PLANS? |