Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK TO CLEAR RECONNECT 2) PLEASE HAVE TEP MAKE PERMANENT SPLICES ON SERVICE DROP | |
| 04/23/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) FOR RECONNECT OF POWER, DWELLING MUST HAVE WORKING HEATING AND COOLING. INSTALL COOLER OR A/C, WIRE PER NEC WITH APPROVED WEATHER PROOF BOXES AND FITTINGS IF OUTSIDE 2) INSTALL SMOKE DETECTORS IN EACH BEDROOM. 3' AWAY FROM REGISTERS 3) SERVICE IS UNGROUNDED, INSTALL GROUNDING SYSTEM, BOND WATER AND GAS PER NEC 4) GROUNDING TYPE RECEPTACLES INSTALLED ON AN UNGROUNDED SYSTEM |