Permit: T04EL00801

Parcel: 12112060B


Addresses:

5123 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/05/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK TO RECONNECT
05/04/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) FILL UNUSED OPENINGS IN PANEL-KO'S, GUTTERS AND FILLER BLANKS 2) PLEASE LABEL NEW DISCONNECT AND INSTALL LOCK NUT CORRECTLY 3) A HOLDOWN DEVICE IS NEEDED FOR MAIN BREAKER 4) COMPLETE #1 OF PREVIOUS INSPECTION. ADDRESS TO BE PERMANENT 5) BACK ROOM STILL LOCKED-PLEASE PROVIDE ACCESS 6) INTERIOR IS OK
05/03/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) LOCKED NO ACCESS-DUE TO WORK LOAD SCHEDULING 2) PM INSPECTION WAS NOT POSSIBLE
04/23/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PLEASE POST ADDRESS ON BLDG 2) MAINTAIN WORKING CLEARANCES AT SERVICE 3) MISSING PANEL COVER AND MAIN DISCONNECTING MEANS 4) DISCONNECT HANDLE HAS BEEN CUT OFF-REPLACE 5) FILL UNUSED OPENINGS IN PANEL IN DINING ROOM, KITCHEN 6) MISSING RECEPTACLE COVER 7) EXTENTION CORDS NOT ALLOWED FOR PERMANENT WIRING 8) A LICENSED ELECTRICAL CONTRACTOR TO DO WORK