Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04EL00799

Parcel: 136171010


Addresses:

8538 E MORMON DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/14/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK TO CLEAR FINAL
05/06/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ CONTRACTOR WILL NEED TO COORDINATE WITH TEP TO OPEN METER COMPARTMENT FOR REMAINDER OF INSPECTION.
05/05/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/. LOCKED. Will make call tomorrow AM since my stop was after hours.
04/29/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PERMANENT ADDRESS TAG (PER CITY AMEND.) 2) MUST BOND NIPPLE AT BOTH ENDS W/A GROUNDING BUSHING AND BONDING JUMPER 3) STRAP GROUND WIRE TO WALL 4) NEED BOTH GROUND RODS 5) NEED WATER AND GAS BOND 6) NEED GROUNDING BUSHING AND BOND JUMPER AT RISER (IN METER BASE) FOR EMERGENCY SERVICE