Permit: T04EL00795

Parcel: 113043490


Addresses:

1216 E NAVAJO RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/04/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/29/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/27/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The bonding is not per code.| 235*/ 1) THE ADDRESS ON THE PANEL IS NOT ON. MUST BE EMBOSSED METAL STRIP. 2) THE GROUND WIRE MUST BE A CONTINUOUS LENGTH, WITHOUT CUTS, ONE PIECE, FROM PANEL TO GROUND RODS. 3) DO NOT USE PENCIL, PEN, MAGIC MARKER OR ANY OTHER NON-METAL ITEM TO APPLY ADDRESS TO PANEL.
04/26/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*/ 1) THE GROUNDING IS NOT PER CODE. SEE TYPICAL DIAGRAM ON PAPER COPY. 2) THE MAIN PANEL NEEDS A METAL ADDRESS TAG ABOVE OR BELOW METER BASE. 3) THE GROUND WIRE AT THE ROD CLAMP MUST BE PLACED IN THE POCKET OPPOSITE THE BOLT. - DRIVE RODS 2" BELOW GROUND LEVEL. LEAVE EXPOSED FOR INSP. GROUND THE WIRE TO EACH ROD AND CONTINUE RUN OF WIRE TO COLD WTR AND GAS PIPES AT WTR HTR.