Permit: T04EL00775

Parcel: 12213258A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/14/2004 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING
11/12/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection. Contractor is ? electric llc. Use approved method for termination of grounding conductor. Breaker to be listed for use by manufacturer
10/21/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
10/18/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) UNLESS A LICENSED ELECTRICAL CONTRACTOR IS OBTAINED TO VERIFY REPAIRS POWER WILL BE DISCONNECT AND LOCKED OUT WITH 5 DAYS. LEFT NOTICE WITH MANAGER. OCCUPANT IS NOT OWNER
10/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspections
09/21/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* NEED ACCESS- ASK TO WAIT UNTIL ? IS HERE
07/28/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PANEL IN TRAILER USING NEUTRAL AS HOT AND BLACK AND GREEN TIE TOGETHER. CORD WIRED INCORRECTLY. OBTAIN THE SERVICES OF A LICENSED ELECTRICAL CONTRACTOR TO CORRECT AND RECALL. INSTALL CORRECT SCREW ON DEAD FRONT COVER AT PANEL
07/21/2004 ELECTRIC - FINAL Denied IVRS - Inspection :The wiring is not complete or does not comply with code.| 245* DEAD FRONT COVER MISSING FOR INSIDE PANEL
07/08/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) FILL UNUSED OPENING IN BOTTOM OF PEDESTAL 2) LABEL BREAKERS 3) NEED ACCESS PER #5 PREVIOUS
06/25/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) USE CORRECT ENTRANCE TO PEDISTALL. 2) USE SINGLE POLE BREAKER 30 AMP NOT 2 POLE. 3) WIRE TO BE SIZED PER CORRECT AMPACITY. 4) DEVICE JUNTION BOX TO BE GROUNDED. 5) NEED ACCESS TO INTERIOR PANEL CONNECTIONS.