Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/23/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 04/21/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) GROUND SCREW NOT TO BE SHEET METAL 250-8. 2) CLEAN SURFACE UNDER LUG 250-12. 3) GRAY CONDUCTOR TO BREAKER TO BE IDENTIFY BLACK - GRAY IS A GROUNDED CONDUCTOR BY 200-7. |