Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T04EL00755
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/15/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
09/14/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/NOTES: 1)INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO COVER 2)GROUND RODS ARE ALLOWED AT 45 DEGREES MAX ANGLE, GROUND ROD CLOSEST TO SERVICE AT MUCH OF ANGLE 3)NEED TO VERIFY WATER & GAS PIPING BOND TO SERVICE. 4)I.D. CIRCUIT BREAKERS |