Permit: T04EL00754

Parcel: 126133680


Addresses:

4502 E 18TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/25/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/27/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/19/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ ROD CONNECTIONS LOOSE AND ON WRONG SIDE OF CLAMP. RODS MUST BE A MIN. OF 6' APART. RODS MUST BE MIN. OF 8' IN LENGTH. NEED MAIN BREAKER RETAINER FOR BACKED BREAKER. A PERMANENT METAL ADDRESS TAG IS REQUIRED. A PERMANENT METAL PLAQUE IS REQUIRED TO DENOTE NUMBER OF SERVICES AND LOCATION THEREOF, 230-2 (E). CALLED BACK - CALLED CONTRACTOR - BOTH SERVICES WILL NEED TO BE GROUPED TOGETHER 230-72 - LADY (ANGEL) WILL TALK TO INSTALLER.