Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/25/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/27/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/19/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*/ ROD CONNECTIONS LOOSE AND ON WRONG SIDE OF CLAMP. RODS MUST BE A MIN. OF 6' APART. RODS MUST BE MIN. OF 8' IN LENGTH. NEED MAIN BREAKER RETAINER FOR BACKED BREAKER. A PERMANENT METAL ADDRESS TAG IS REQUIRED. A PERMANENT METAL PLAQUE IS REQUIRED TO DENOTE NUMBER OF SERVICES AND LOCATION THEREOF, 230-2 (E). CALLED BACK - CALLED CONTRACTOR - BOTH SERVICES WILL NEED TO BE GROUPED TOGETHER 230-72 - LADY (ANGEL) WILL TALK TO INSTALLER. |