Permit: T04EL00734

Parcel: 123152240

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/06/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
04/14/2004 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) PANEL INSTRUCTIONS ON INSIDE COVER DO NOT ALLOW LOAD CONDUCTORS TO ENTER THRU TOP END WALL SEE SENTENCE CIRCLED MUST BE ON SIDE AND IF ABOVE BUS USE A SEALING LOCK NUT 2) OLD SE CABLE EXITING THRU LB'S MUST BE COVERED TO PROTECT 3) PLATE BOARDS BEING USED TO SUPPORT 2-HOLE STRAPS ON INSUFFICIENT STRENGTH TO HOLD RISER FIND STRONGER SUPPORT