Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/06/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection :* |
| 04/14/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) PANEL INSTRUCTIONS ON INSIDE COVER DO NOT ALLOW LOAD CONDUCTORS TO ENTER THRU TOP END WALL SEE SENTENCE CIRCLED MUST BE ON SIDE AND IF ABOVE BUS USE A SEALING LOCK NUT 2) OLD SE CABLE EXITING THRU LB'S MUST BE COVERED TO PROTECT 3) PLATE BOARDS BEING USED TO SUPPORT 2-HOLE STRAPS ON INSUFFICIENT STRENGTH TO HOLD RISER FIND STRONGER SUPPORT |