Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/10/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210$ 1. BOND GAS PIPE ON LOAD SIDE OF METER AND REMOVE PAINT UNDER CLAMP 2. BY RUNNING A #4 BARE CU BETWEEN SERVICE AND PANEL "B" YOU HAVE CREATED A PARALLEL PATH - PANEL "B" SHOULD ONLY HAVE NEUTRAL, EQUIPMENT GROUND, AND GROUND RODS CONNECTED TO IT. THE EQUIPMENT GROUND IN THIS PANEL SHOULD SERVE AS THE WATER AND GAS PIPE BOND PATH BACK TO THE SERVICE. |