Permit: T04EL00690

Parcel: 123150870


Addresses:

826 E LEE ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04EL00690

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK TO CLEAR
04/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) UPGRADE SERVICES ARE REQUIRED TO BE MINIMUM 100 AMPS THE WIRE IS OK THE MAIN CB IS ONLY 60 AMPS 2) WHEN A CIRCUIT BREAKER IS BACK FED NEC REQUIRES A FASTENER TO HOLD CB IN PLACE 3) RISER DOES NOT EXTEND ABOVE ROOF REQUIRED DISTANCE TO CLEAR ROOF 4) PANEL HAS TO BE LISTED FOR SERVICE EQUIPMENT USE 5) GROUND RODS REQUIRED BY NEC TO BE DRIVEN TO GRADE OR BELOW TO ELIMINATE TRIP HAZARD
04/07/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ 1) THE ELECTRICAL EQUIPMENT DOES NOT MEET TUCSON ELECTRIC POWER COMPANY SER REQUIREMENTS. CONTACT TEP CONSTRUCTION OFFICE FOR DIRECTION 2) THE MAIN REQUIRES A SERVICE MAIN CIRCUIT BREAKER. SEE NEC ART. 230 3) THE METER BOX MUST BEAR A METAL STRIP ADDRESS 4) THE CHASE NIPPLE REQUIRES A BOND BUSHING IN PANEL SIDE 5) THE GROUND WIRE MUST BE SUPPORTED TO WALL WITH A MINIMUM OF TWO STRAPS 6) THE GAS PIPE MUST BE BONDED TO PANEL GROUND 7) SERVICE RISER MUST BE EXTENDED ABOVE ROO. IT I TO CLOSE TO GROUND