Permit: T04EL00661

Parcel: 133030990

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/13/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/07/2004 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*/ 1) A WATER BOND IS NEEDED 2) BONDING DEVICE IS NEEDED ON BOTH SIDES OF NIPPLE 250.94 3) GROUNDING EQUIPMENT CONDUCTORS TO BE NO MORE THAN 2 PER TERMINAL LUG AS PER MANUFACTURERS LABEL 4) USE CORRECT SIZED BREAKER FOR CONDUCTOR AMPACITY 5) DRY WALL SCREWS NOT APPROVED HARDWARE FOR SUPPORT