Permit: T04EL00649

Parcel: 140270220

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/05/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. 2) I.D. ALL CIRCUIT BREAKERS. 3) CIRCUIT BREAKERS TO ALL BE G.E. BRAND. 4) SUPPORT SEALTITE FLEX TO WTR HTR. 5) USE ΒΌ" MIN. BOLTS TO SUPPORT RISER. 6) USE SUNLITE RESISTENT CONDUCTORS FOR RISER FEEDERS, MUST BE VISIBLY MARKED ON CONDUCTOR INSULATION, 310-11 NEC.