Permit: T04EL00648

Parcel: 115080040


Addresses:

105 E MABEL ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) OK TO CLEAR
04/15/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) NO ENTRANCE ALLOWED THROUGH METER SECTION PER MANUFACTURER AND CODE 230-7. 2) RE-LABEL BREAKERS TO CIRCUITS. 3) ROCKS BELOW SERVICE CREATE AN UNSAFE WORKING AREA 110-26. 4) COMPLETE #2 OF PREVIOUS INSP.
04/05/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ CORRECTIONS REQUIRED: 1) INSTALL METAL ADDRESS STRIP OR NUMBERS. DO NOT USE PEN, PENCIL OR MAGIC MARKER, ETC. 2) INSTALL NEW GROUNDING SYSTEM CONSISTING OF TWO 5/8"X8' COPPER CLAD GROUND RODS SET 6' APART. BOND GAS PIPE AND WTR PIPE AT POINT WHERE PIPE ENTERS HOUSE. 3) ADD A LOCK NUT TO NIPPLE ON 1ΒΌ" LB INSIDE PANEL, BEFORE GROUND BUSHING. 4) BRANCH CIRCUIT BREAKERS MUST BE MURRAY PER INSTRUCTION SHEET ON PANEL COVER. CHANGE OUT SIEMENS C/BS.