Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/04/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection :*/ 1) OK TO CLEAR 2) OWNER TO DRIVE GROUND ROD TO GRADE OR BUILD UP AROUND IT |
| 04/02/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*/ 1) 2 GROUND RODS REQUIRED 6' MIN. APART 45o MAX ANGLE IF NOT VERTICLE. 2) I.D. ALL CIRCUIT BREAKERS. 3) INSTALL BUSHING IN BACK K.O. OF ENCLOSURE. 4) SUPPORT GFCI OUTLET BOX. 5) STRAP #4 BARE TO WALL OF HOUSE. 6) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE, MUST BE SCREWED OR RIVITED. 7) INSTALL ROMEX CONNECTOR AT ROMEX TERMINATION 4X4 W/P BOX. 8) SUPPORT RISER WITHIN 3' OF TERMINATION, USE ΒΌ" MIN. HARDWARE. |