Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04EL00581
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/01/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
03/26/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215*/ 1-A THE SERVICE RISER MUST HAVE TWO SUPPORTS, THE FIRST WITHIN 8" OF PANEL TOP. 1-B CONTACT TEP CUSTOMER SERVICE AND REQUEST AN INSPECTION OF THE ELECTRICAL EQUIPMENT LOCATION AND POINT OF ATTACHMENT. THEY HAVE REQUIREMENTS WHICH YOUR NEW INSTALLATION MAY NOT BE IN COMPLIANCE OF - AS INSTALLED. 2) A PERM. METAL ADDRESS TAG MUST BE ATTACHED TO THE METER SIDE OF THE PANEL. USE SCREWS OR RIVETS. DO NOT USE MAGIC MARKER, SHARPIES, PEN, PENCIL OR CRAYON. 3) THE PANEL AND SUPPORTING BOARDS MUST BE FIRMLY ATTACHED TO THE WALL WITH FASTENERS NOT LESS THAN ΒΌ" SIZE. 4) THE WTR PIPING AND THE GAS PIPING MUST BE GROUNDED TO THE GROUNDING SYSTEM. ATTACH TO THE HOUSE SIDE PIPES. 5) THE GROUND RODS MUST BE LOCATED IN EARTH GRADE FOR THIER ENTIRE LENGTH. INSTALLATION IN ELEVATED FLOWER PLANTERS IS NOT ACCEPTABLE. THE GROUND WIRE SHOULD BE IN THE CLAMP POCKET OPPOSITE THE CLAMP BOLT. |